Skip to main content
Electrical Maintenance

Low Voltage Switchgear Maintenance Checklist

A maintenance checklist for LV switchgear and main switchboards covering thermographic surveys, circuit breaker testing, busbar inspection, and protection device verification for commercial buildings.

What is a lv switchgear maintenance checklist?

A low voltage switchgear maintenance checklist is a structured list of the 10 preventive maintenance tasks — covering visual, functional, safety and record-keeping checks — that keep a low voltage switchgear running safely and reliably. It groups routine checks by frequency, from daily inspections to annual servicing, so FM teams and building engineers can plan and evidence preventive maintenance.

Core lv switchgear checks

  • Visual inspection for signs of overheating, arcing, or damage
  • Perform thermographic survey of all panels and connections
  • Check earth bonding connections
  • Record load readings on main incomer and major outgoing circuits

What is a low voltage switchgear?

Low voltage switchgear distributes electrical power from the transformer or main intake throughout the building at 400/230V. It includes the main LV switchboard, moulded case circuit breakers (MCCBs), air circuit breakers (ACBs), busbars, and metering equipment. LV switchgear is the heart of the building's electrical distribution and requires regular maintenance to ensure safety and reliability.

This checklist is one of 16 in our electrical maintenance checklists, covering distribution boards, switchgear, generators, UPS, solar PV and EV charging — inspection, testing and thermographic checks.

Typical LV switchgear maintenance checklist

A practical starting point for planned preventive maintenance. Always refer to the manufacturer's O&M manual and site-specific requirements.

Low Voltage Switchgear maintenance checklist showing tasks such as circuit breaker servicing (on shutdown) and busbar connection torque checks, each with its service frequency
A preview of the LV switchgear maintenance checklist — the full 10-task routine, service frequencies and safety notes are below, free to download as a PDF.

Visual Checks

  • Visual inspection for signs of overheating, arcing, or damage
  • Check panel ventilation and cooling fans are operational
  • Check all labels and circuit schedules are accurate and legible
  • Inspect cable entries and glands for condition and tightness

Functional Checks

  • Perform thermographic survey of all panels and connections
  • Verify RCD and RCBO devices trip within specified time using test button

Safety Checks

  • Check earth bonding connections
  • Verify the switchroom is clean, dry, and free of stored materials

Record Keeping

  • Record load readings on main incomer and major outgoing circuits
  • Review the latest periodic electrical inspection report (EICR)

Download the free LV switchgear maintenance checklist PDF

Get all 10 tasks as a printable PDF — free, no signup needed. Keep a copy in the plant room, attach it to work orders, or share it with your maintenance contractor.

Typical maintenance frequency

Suggested intervals for low voltage switchgear maintenance. Actual frequencies should follow manufacturer guidance and site-specific risk assessments.

Annually

  • Thermographic survey
  • Visual inspection
  • Load recording
  • RCD testing
  • Switchroom housekeeping check

Every 6 Months

  • Circuit breaker servicing (on shutdown)
  • Busbar connection torque checks
  • Insulation resistance testing
  • Protection coordination review

Common faults and issues

Issues to be aware of when maintaining low voltage switchgear equipment.

Loose busbar connections causing localised overheating — detectable by thermography
Circuit breaker nuisance tripping from incorrect settings or ambient temperature effects
Out-of-date circuit schedules causing confusion during fault finding
RCD devices failing to trip within required time due to deterioration
Switchroom used for storage, restricting access and creating fire risks

Safety and compliance notes

Key safety considerations for low voltage switchgear maintenance. This is general guidance only — always follow OEM instructions, statutory requirements, and your organisation's safe systems of work.

LV electrical work must be carried out by competent persons following safe systems of work
Switchrooms must be kept locked, clean, and free of flammable materials and stored items
Arc flash hazards exist at LV — use appropriate PPE for the prospective fault current
Periodic electrical inspection (EICR) is required under BS 7671 — ensure it is current

Reference standards and frameworks

United Kingdom
BS 7671 (IET Wiring Regulations) and the Electricity at Work Regulations 1989
North America
NFPA 70B (electrical equipment maintenance) and ANSI/NETA MTS

Frameworks commonly referenced when planning lv switchgear maintenance programmes. Always confirm the requirements that apply to your site and jurisdiction.

How PM Assist helps

Managing LV switchgear documentation with PM Assist

PM Assist helps FM and building operations teams search their O&M manuals and building drawings in seconds. Upload your low voltage switchgear documentation and ask questions like “When was the last inspection carried out?” or “What are the rated specifications?” — and get source-cited answers instantly.

See PM Assist answer questions about a real lv switchgear manual — try the live demo, no signup needed.

Take this checklist with you

Download the branded PDF, generate a custom version for your asset, or run AI search across all your building documentation.

Generate a custom checklist

Inspection checklists for this asset

Maintenance keeps the asset working; a statutory inspection records whether it currently passes. Both usually apply.

Frequently asked questions

How often should LV switchgear be inspected?
Annual thermographic surveys and visual inspections are recommended. Full maintenance (shutdowns for breaker servicing, torque checks, and insulation testing) is typically every 3–5 years. BS 7671 recommends periodic inspection and testing at intervals appropriate to the installation type — typically every 5 years for commercial premises.
What is an EICR?
An Electrical Installation Condition Report (EICR) is a formal report on the condition of the electrical installation, carried out by a competent person in accordance with BS 7671. It identifies defects, potential dangers, and deviations from current standards. EICRs are legally required for many commercial premises.
Why is thermography important for switchgear?
Thermographic surveys detect hot spots at connections, busbars, and breaker contacts before they cause failures or fires. A loose connection generates heat that increases over time and can eventually cause arcing, fire, or equipment damage. Annual thermography is one of the most cost-effective preventive maintenance activities for electrical systems.

Manage your building documentation with AI

PM Assist gives FM teams instant access to O&M manuals, drawings, and maintenance knowledge — all searchable with AI.

  • Upload and organise building documentation
  • AI-powered search across all your manuals
  • Source-cited answers for maintenance queries
  • Team collaboration and access control
  • No credit card required to start