HFC/HFO blend (zeotropic) · ASHRAE 34 safety group A2L

R-454B GWP and CO₂e

R-32 / R-1234yf blend — R-32/1234yf (68.9/31.1). Current. An A2L — mildly flammable — so it brings ventilation, leak-detection and safe-working requirements the A1 refrigerant it replaces did not.

Great Britain

466.3

Computed per retained Regulation (EU) No 517/2014, Annex IV, from Annex I/II component values

EU / Northern Ireland

465.2

Computed per Regulation (EU) 2024/573, Annex VI, from Annex I/II component values

These two figures genuinely differ. Use the one for the regime the equipment is in — Great Britain, or Northern Ireland under the Windsor Framework.

How this number is arrived at

R-454B is a blend, so neither regulation lists a GWP for it directly. Both set out the same method — a mass-weighted average of the components — and both list the component values in their own annexes. The arithmetic is below so you can check it rather than take it on trust.

Component% by massGWP (GB)GWP (EU/NI)
R-3268.9%675675
R-1234yf31.1%40.501

Great Britain: (0.689 × 675) + (0.311 × 4) = 465.075 + 1.244 = 466.3

EU / Northern Ireland: (0.689 × 675) + (0.311 × 0.501) = 465.075 + 0.156 = 465.2

Composition from ASHRAE Standard 34, as published in the ASHRAE Handbook—Fundamentals refrigerants chapter. Method from Regulation (EU) 2024/573 Annex VI and the retained GB Annex IV, which are worded identically.

Charge in kg → tonnes CO₂e

t CO₂e = charge (kg) × GWP ÷ 1,000. This figure, not the charge in kilograms, is what sets the statutory leak-check frequency.

Charget CO₂e (GB)t CO₂e (EU/NI)
1 kg0.470.47
2 kg0.930.93
5 kg2.332.33
10 kg4.664.65
20 kg9.339.30
50 kg23.3223.26
100 kg46.6346.52

Leak-check thresholds in kg

The regulations set the bands in tonnes CO₂e. Converted to a charge of R-454B, the duty starts at these weights.

BandCharge (GB)Charge (EU/NI)Check at leastWith leak detection
≥5 t CO₂e10.7 kg10.7 kgAt least every 12 monthsEvery 24 months
≥50 t CO₂e107 kg107 kgAt least every 6 monthsEvery 12 months
≥500 t CO₂e1,072 kg1,075 kgAt least every 3 monthsEvery 6 months

Automatic leak detection is mandatory at 500 tonnes CO₂e and above. Hermetically sealed equipment labelled as such is exempt below 10 tonnes CO₂e. Records must be kept for at least five years. Sources: retained Regulation (EU) No 517/2014 Articles 4–6, Regulation (EU) 2024/573 Articles 5–7, and GOV.UK guidance on checking F-gas equipment for leaks.

The two figures differ only because R-1234yf is valued differently in each regime's Annex II — 4 in GB, 0.501 in the EU and Northern Ireland. The R-32 component is identical. Note also that the widely quoted 467 comes from the ASHRAE Handbook on an AR5 basis, which is not the basis either regulation uses.

Where you meet R-454B

  • •New air-cooled chillers and heat pumps replacing R-410A
  • •Rooftop and packaged units of current manufacture
  • •New VRF where A2L is permitted by the ventilation and safety assessment

Maintenance checklists for plant that runs on it

Frequently asked questions

What is the GWP of R-454B?
It depends which regime you are in. In Great Britain it is 466.3; in the EU and Northern Ireland it is 465.2. Both are correct — they come from different annexes valuing the same substance on different assessment-report bases, and the page above cites each one.
How do I convert an R-454B charge into tonnes CO₂e?
Multiply the charge in kilograms by the GWP and divide by 1,000. A 10 kg charge of R-454B is 4.66 tonnes CO₂e in Great Britain and 4.65 tonnes in Northern Ireland. That figure is what sets the statutory leak-check frequency, not the charge in kilograms.
At what charge does R-454B need leak checks?
The duty starts at 5 tonnes CO₂e, which for R-454B is about 10.7 kg in Great Britain. Six-monthly checks start at 50 tonnes (107 kg) and quarterly at 500 tonnes (1,072 kg), where an automatic leak detection system also becomes mandatory. Fitting leak detection doubles the interval at every band. Hermetically sealed equipment labelled as such is exempt below 10 tonnes CO₂e.
Does R-454B work differently in Northern Ireland?
The two figures differ only because R-1234yf is valued differently in each regime's Annex II — 4 in GB, 0.501 in the EU and Northern Ireland. The R-32 component is identical. Note also that the widely quoted 467 comes from the ASHRAE Handbook on an AR5 basis, which is not the basis either regulation uses.
Where is R-454B used?
New air-cooled chillers and heat pumps replacing R-410A; Rooftop and packaged units of current manufacture; New VRF where A2L is permitted by the ventilation and safety assessment. Current. An A2L — mildly flammable — so it brings ventilation, leak-detection and safe-working requirements the A1 refrigerant it replaces did not.