R-410A GWP and CO₂e
R-32 / R-125 blend — R-32/125 (50/50). Restricted in new equipment under the F-Gas phase-down. Servicing existing plant continues, increasingly from reclaimed stock.
Great Britain
2,088
Computed per retained Regulation (EU) No 517/2014, Annex IV, from Annex I/II component values
EU / Northern Ireland
2,088
Computed per Regulation (EU) 2024/573, Annex VI, from Annex I/II component values
The figure is the same in both regimes. Both state their values on an IPCC Fourth Assessment Report basis for this substance, so a number quoted from AR5 or AR6 will not match the one that governs compliance.
How this number is arrived at
R-410A is a blend, so neither regulation lists a GWP for it directly. Both set out the same method — a mass-weighted average of the components — and both list the component values in their own annexes. The arithmetic is below so you can check it rather than take it on trust.
| Component | % by mass | GWP (GB) | GWP (EU/NI) |
|---|---|---|---|
| R-32 | 50% | 675 | 675 |
| R-125 | 50% | 3500 | 3500 |
Great Britain: (0.50 × 675) + (0.50 × 3500) = 337.5 + 1750 = 2087.5, reported as 2088
EU / Northern Ireland: (0.50 × 675) + (0.50 × 3500) = 337.5 + 1750 = 2087.5, reported as 2088
Composition from ASHRAE Standard 34, as published in the ASHRAE Handbook—Fundamentals refrigerants chapter. Method from Regulation (EU) 2024/573 Annex VI and the retained GB Annex IV, which are worded identically.
Charge in kg → tonnes CO₂e
t CO₂e = charge (kg) × GWP ÷ 1,000. This figure, not the charge in kilograms, is what sets the statutory leak-check frequency.
| Charge | t CO₂e (GB) | t CO₂e (EU/NI) |
|---|---|---|
| 1 kg | 2.09 | 2.09 |
| 2 kg | 4.18 | 4.18 |
| 5 kg | 10.44 | 10.44 |
| 10 kg | 20.88 | 20.88 |
| 20 kg | 41.76 | 41.76 |
| 50 kg | 104.40 | 104.40 |
| 100 kg | 208.80 | 208.80 |
Leak-check thresholds in kg
The regulations set the bands in tonnes CO₂e. Converted to a charge of R-410A, the duty starts at these weights.
| Band | Charge (GB) | Charge (EU/NI) | Check at least | With leak detection |
|---|---|---|---|---|
| ≥5 t CO₂e | 2.39 kg | 2.39 kg | At least every 12 months | Every 24 months |
| ≥50 t CO₂e | 23.9 kg | 23.9 kg | At least every 6 months | Every 12 months |
| ≥500 t CO₂e | 239 kg | 239 kg | At least every 3 months | Every 6 months |
Automatic leak detection is mandatory at 500 tonnes CO₂e and above. Hermetically sealed equipment labelled as such is exempt below 10 tonnes CO₂e. Records must be kept for at least five years. Sources: retained Regulation (EU) No 517/2014 Articles 4–6, Regulation (EU) 2024/573 Articles 5–7, and GOV.UK guidance on checking F-gas equipment for leaks.
Where you meet R-410A
- •Commercial air conditioning installed roughly 2005–2024
- •Small and mid-size air-cooled chillers
- •VRF systems of that generation
- •Packaged rooftop units