R-134a GWP and CO₂e
1,1,1,2-tetrafluoroethane. Restricted in new equipment under the F-Gas phase-down, and widely displaced by R-513A and R-1234ze on new chillers. Servicing existing plant continues.
Great Britain
1,430
Retained Regulation (EU) No 517/2014, Annex I (AR4 basis)
EU / Northern Ireland
1,430
Regulation (EU) 2024/573, Annex I (AR4 basis, footnote 2)
The figure is the same in both regimes. Both state their values on an IPCC Fourth Assessment Report basis for this substance, so a number quoted from AR5 or AR6 will not match the one that governs compliance.
Charge in kg → tonnes CO₂e
t CO₂e = charge (kg) × GWP ÷ 1,000. This figure, not the charge in kilograms, is what sets the statutory leak-check frequency.
| Charge | t CO₂e (GB) | t CO₂e (EU/NI) |
|---|---|---|
| 1 kg | 1.43 | 1.43 |
| 2 kg | 2.86 | 2.86 |
| 5 kg | 7.15 | 7.15 |
| 10 kg | 14.30 | 14.30 |
| 20 kg | 28.60 | 28.60 |
| 50 kg | 71.50 | 71.50 |
| 100 kg | 143.00 | 143.00 |
Leak-check thresholds in kg
The regulations set the bands in tonnes CO₂e. Converted to a charge of R-134a, the duty starts at these weights.
| Band | Charge (GB) | Charge (EU/NI) | Check at least | With leak detection |
|---|---|---|---|---|
| ≥5 t CO₂e | 3.50 kg | 3.50 kg | At least every 12 months | Every 24 months |
| ≥50 t CO₂e | 35.0 kg | 35.0 kg | At least every 6 months | Every 12 months |
| ≥500 t CO₂e | 350 kg | 350 kg | At least every 3 months | Every 6 months |
Automatic leak detection is mandatory at 500 tonnes CO₂e and above. Hermetically sealed equipment labelled as such is exempt below 10 tonnes CO₂e. Records must be kept for at least five years. Sources: retained Regulation (EU) No 517/2014 Articles 4–6, Regulation (EU) 2024/573 Articles 5–7, and GOV.UK guidance on checking F-gas equipment for leaks.
Where you meet R-134a
- •Large water-cooled centrifugal chillers
- •Mid-size screw chillers
- •Medium-temperature commercial refrigeration