R-32 GWP and CO₂e
Difluoromethane. Current. The mainstream lower-GWP replacement for R-410A in splits, VRF and small packaged plant.
Great Britain
675
Retained Regulation (EU) No 517/2014, Annex I (AR4 basis)
EU / Northern Ireland
675
Regulation (EU) 2024/573, Annex I (AR4 basis, footnote 2)
The figure is the same in both regimes. Both state their values on an IPCC Fourth Assessment Report basis for this substance, so a number quoted from AR5 or AR6 will not match the one that governs compliance.
Charge in kg → tonnes CO₂e
t CO₂e = charge (kg) × GWP ÷ 1,000. This figure, not the charge in kilograms, is what sets the statutory leak-check frequency.
| Charge | t CO₂e (GB) | t CO₂e (EU/NI) |
|---|---|---|
| 1 kg | 0.68 | 0.68 |
| 2 kg | 1.35 | 1.35 |
| 5 kg | 3.38 | 3.38 |
| 10 kg | 6.75 | 6.75 |
| 20 kg | 13.50 | 13.50 |
| 50 kg | 33.75 | 33.75 |
| 100 kg | 67.50 | 67.50 |
Leak-check thresholds in kg
The regulations set the bands in tonnes CO₂e. Converted to a charge of R-32, the duty starts at these weights.
| Band | Charge (GB) | Charge (EU/NI) | Check at least | With leak detection |
|---|---|---|---|---|
| ≥5 t CO₂e | 7.41 kg | 7.41 kg | At least every 12 months | Every 24 months |
| ≥50 t CO₂e | 74.1 kg | 74.1 kg | At least every 6 months | Every 12 months |
| ≥500 t CO₂e | 741 kg | 741 kg | At least every 3 months | Every 6 months |
Automatic leak detection is mandatory at 500 tonnes CO₂e and above. Hermetically sealed equipment labelled as such is exempt below 10 tonnes CO₂e. Records must be kept for at least five years. Sources: retained Regulation (EU) No 517/2014 Articles 4–6, Regulation (EU) 2024/573 Articles 5–7, and GOV.UK guidance on checking F-gas equipment for leaks.
Where you meet R-32
- •Split and multi-split air conditioning
- •VRF and VRV systems installed from around 2015
- •Small packaged and rooftop units
- •Air-to-water heat pumps