R-1234yf GWP and CO₂e
2,3,3,3-tetrafluoropropene. Current, very low GWP. Mostly encountered in buildings as the low-GWP half of a blend such as R-454B or R-513A.
Great Britain
4
Retained Regulation (EU) No 517/2014, Annex II (Montreal Protocol SAP 2010)
EU / Northern Ireland
0.501
Regulation (EU) 2024/573, Annex II (AR6 basis, footnote 2)
These two figures genuinely differ. Use the one for the regime the equipment is in — Great Britain, or Northern Ireland under the Windsor Framework.
Charge in kg → tonnes CO₂e
t CO₂e = charge (kg) × GWP ÷ 1,000. This figure, not the charge in kilograms, is what sets the statutory leak-check frequency.
| Charge | t CO₂e (GB) | t CO₂e (EU/NI) |
|---|---|---|
| 1 kg | 0.00 | 0.00 |
| 2 kg | 0.01 | 0.00 |
| 5 kg | 0.02 | 0.00 |
| 10 kg | 0.04 | 0.01 |
| 20 kg | 0.08 | 0.01 |
| 50 kg | 0.20 | 0.03 |
| 100 kg | 0.40 | 0.05 |
Leak-check thresholds in kg
The regulations set the bands in tonnes CO₂e. Converted to a charge of R-1234yf, the duty starts at these weights.
| Band | Charge (GB) | Charge (EU/NI) | Check at least | With leak detection |
|---|---|---|---|---|
| ≥5 t CO₂e | 1,250 kg | 9,980 kg | At least every 12 months | Every 24 months |
| ≥50 t CO₂e | 12,500 kg | 99,800 kg | At least every 6 months | Every 12 months |
| ≥500 t CO₂e | 125,000 kg | 998,004 kg | At least every 3 months | Every 6 months |
Automatic leak detection is mandatory at 500 tonnes CO₂e and above. Hermetically sealed equipment labelled as such is exempt below 10 tonnes CO₂e. Records must be kept for at least five years. Sources: retained Regulation (EU) No 517/2014 Articles 4–6, Regulation (EU) 2024/573 Articles 5–7, and GOV.UK guidance on checking F-gas equipment for leaks.
This is the sharpest divergence between the two regimes, and it is about duties rather than numbers. Retained Regulation (EU) No 517/2014 defines a fluorinated greenhouse gas, at Article 2(1), as one listed in Annex I; R-1234yf sits in its Annex II, headed "subject to reporting". So in Great Britain it attracts no statutory leak-check duty. Regulation (EU) 2024/573 extends leak checks at Article 5(1) to equipment holding 1 kg or more of an Annex II Section 1 substance, so in Northern Ireland the same system is checked at least every 12 months from 1 kg, every 6 months from 10 kg and every 3 months from 100 kg. Recovery, certification and record-keeping duties are a separate question from containment and are not addressed by this page.
Where you meet R-1234yf
- •Automotive air conditioning
- •A component of several current commercial blends rather than a common building charge in its own right